Electrical installation engineering construction technology

    Construction Program

    General construction procedures:

    Buried pipe, buried parts → equipment installation → wire, cable laying → loop connected → check, test, commissioning → power test run → delivery use

    Oil-immersed power transformer

    Unpacking inspection → Secondary handling → Equipment in place → Core inspection → Attachment installation → Oil filtering, oil injection → Insulation test → Handover test → Acceptance

    Whether the oil-immersed power transformer needs a core inspection should be determined based on the size of the transformer, the manufacturer's specifications, storage time, and whether there is an abnormality in the transportation process.

    Cabinet type vacuum circuit breaker

    Vacuum Circuit Breaker Inspection → Operating Mechanism Check → Vacuum Circuit Breaker In Place → Mechanical and Electrical Performance Test

    Oil circuit breaker

    Unpacking inspection → Main body installation → Operating mechanism installation → Check, adjustment → Insulation test → Test

    Isolation switch

    Unpacking inspection → Main body installation → Operation mechanism installation → Adjustment

    skills requirement

    Installation regulations

    The storage and storage period of the electrical equipment and equipment before installation shall be in accordance with the requirements of the manufacturer. The equipment and equipment shall be securely placed and shall not be damaged. The environmental conditions for safekeeping should include measures such as fire protection, moisture protection, and dust prevention.

    Fasteners for installation of electrical equipment, should use galvanized products

    After the transformer is installed in place, grounding terminals should be well grounded. The current transformer secondary coil that is not to be used temporarily should be short-circuited and then grounded. When installing a zero-sequence instrument transformer, pay special attention to the distance from the surrounding magnetic conductor or charged conductor.

    The reactor is installed so that the winding direction of the coil meets the design requirements

    Insulating oil should be strictly filtered and its electric strength, dielectric loss tangent, chromatographic analysis, etc. can only be injected into the equipment after passing the test.

    Protective grounding and working grounding of electrical equipment must be reliable

    Handover test

    The main function of the transfer test is to determine whether the installation quality of the electrical equipment is qualified, and determine whether the equipment can be put into operation.

    Handover test content

    Measuring insulation resistance

    The greater the insulation resistance, the better the insulation performance

    DC withstand voltage test

    AC withstand voltage test

    The method of identifying the insulation strength of electrical equipment is an important measure to ensure the safe operation of the equipment. Through the test to grasp the insulation of the equipment, the hidden defects inside the insulation are discovered in time.

    Insulation preventive tests are divided into two categories:

    The non-destructive test or insulation characteristic test is a variety of characteristic parameters measured at a lower voltage or with other methods that will not damage the insulation, mainly including measuring the leakage resistance of the insulation resistance, the tangent of the dielectric loss, etc. In order to judge whether there is any defect inside the insulation

    Destructive test or pressure test, the voltage applied in the test is higher than the working voltage of the equipment, and the insulation test is very strict, especially to expose those serious defects that are dangerous, and to ensure that the insulation has a certain degree of electrical strength , Including DC withstand voltage, AC voltage and so on. The disadvantage of pressure test is that ash can cause some damage to insulation.

    Measuring Conductor DC Resistance

    The smaller the conductor DC resistance, the better the conductivity

    Machinery Brackets

    Machinery Brackets ,Metal Brackets ,Metal Shelf Brackets,Steel Brackets

    Ningbo Metal Sharing Supply Chain Management Co., Ltd , https://www.sharescm.com

    Previous Post: Automotive Industry Promotes Rubber Consumption Demand 2018 Synthetic Rubber Production Will Surpass 6 Million Tons
    Next Post: Molybdenum ore beneficiation flotation and grinding process
    Home
    Recent Posts
    • FAW Jiexi Xiecha Hengwei Provides the Strongest …
    • Vortex pump failure solution
    • [Meter's Latest Patent] An Intelligent Water…
    • Commercial vehicles will usher in significant fa…
    • The difference between metal laser cutting machi…
    • Disc Blades for Agriculture Tillage
    • Galvaznied C Shaped Steel Profile Slotted Struct…
    • Rip calcium carbonate crushing line included in …
    • 6.5KW Silent Tpye Dual Fuel Generator Export to …
    • You'an Macro Network Video Surveillance Comm…
    • Plant Resistance to Lodging Tester Promotes Bree…
    • Development Status and Prospect of Electrostatic…
    • Digital Multimeter Product Features
    • Several suggestions for improving the efficiency…
    • Instrument tube valve parts - how little do you …
    • Zoomlion road roller spring benefit, the new dou…
    • What kind of water is high quality water?
    • Industrial PON2.0 builds Industry 4.0 neural net…
    • High-quality rice "cultivation" in min…
    • Bohai Pistons Honored with "Excellent Suppl…